RELTEST 1000
Three Phase Relay Test Set
- Advanced multifunctional relay test set, specially designed for distribution, smart grid and renewable energy plants.
- Local control, via keyboard and coloured display.
- Remote control with the Advanced Test & Data Management Software.
- Three independent AC voltage outputs adjustable from 0 to 400 V.
- Fourth independent AC voltage output adjustable from 0 to 130 V.
- One current output, from 0 to 15 A, switchable on 3 phase sockets.
- One independent current output, adjustable from 0 to 1 A.
- Frequency generator: 40 – 400 Hz.
- Battery simulator.
- Two separate timer inputs.
- Four auxiliary relay outputs.
- Optional IEC 61850-8 communication interface.
- Optional six low level outputs.
- Coloured graphic display and local control.
- USB interface.
- Internal memory for test results storage and saving.
- Automatic test report.
- Light and easy to carry
SKU: 042
Categoría: Ensayos y Mediciones
Etiquetas: Ensayo de Protecciones, Ensayos de Protecciones e Interruptores
Aplication
The use of RELTEST is extremely easy: once conenctions are performed, the operator can select the desidered test by a menu. Tests can be performed locally or by PC control. Test results are automatically saved and then downloaded in the PC using the software TDMS, provided with the test equipment, for final storage and printing.
TECHNICAL SPECIFICATIONS
THREE VOLTAGE OUTPUTS
- Three AC voltage outputs, separately adjustable. Output range (phase voltage): from 0 V to 100 V AC o 400 V AC.
- Connection: 4 safety sockets (3 phases and a common neutral).
- Possibility to set the amplitude of the outputs independently for each output, continuously.
- Accuracy: ± 0,5% of the output, ± 0,2% of the range.
- Distorsion: 0,1%.
- Angles between the voltages: adjustable from 0° to 360 °.
- Resolution: 0,5°; accuracy: 1°.
- Voltage outputs have the neutral in common and are isolated from mains and ground.
- Power available for each phase: 20 VA continuously, at the maximum voltage.
- Possibility to set independently the pre-fault and the fault output amplitudes.
FOURTH VOLTAGE GENERATOR
The test equipment is provided with a fourth voltage output, with the neutral in common with the three phase voltages, adjustable separately from the phase voltages.
- Voltage ranges: 13 V or 130 V AC.
- Possibility to set the output amplitide from zero to the maximum value, continuously.
- Connection: 2 safety sockets.
- Accuracy: ± 0,5% of the output, ± 0,2% of the range.
- Resolution: 6 mV on the 13 V range, 60 mV on the 130 V range.
- Distortion: 0,1%.
- Angle: adjustable from 0° to 360°.
- Resolution: 0,5°; accuracy: 1°.
- The output is isolated from mains and ground.
- Available power: 6 VA continuously, at the maximum voltage.
- Possibility to set independently the pre-fault and the fault output amplitudes.